EM600 High-Performance Vector Control Inverter User Manual Under vector control mode, inverter adjusts speed dynamic response of vector control by adjusting PI regulator’s speed proportional gain (ASR_P) and speed integral time (ASR_T). Either increasing ASR_P or reducing ASR_T would quicken velocity loop's dynamic response. However, if ASR_P is excessive or ASR_T is insufficient or excessive, this will result in oscillation due to over regulation. User shall adjust the aforesaid PI parameters according to actual load characteristics. Generally, user shall increase ASR_P as possible and regulate ASR_T, so as to enable the system to response quickly without over control.
To enable the system to have a quick dynamic response at both low speed and high speed, it's required to perform PI regulation at both speed modes. In actual running, speed regulator would automatically calculate present PI parameter according to present frequency. If present PI parameter is below switching frequency 1, speed PI parameter is P1, T1; if above switching frequency 2, speed parameter PI is P2, T2. If greater than switching frequency 1(F06.04), but less than switching frequency 2 (F06.05), the movement from switching frequency 1 to switching frequency 2 presents a linear transition procedure. See Figure 7-22.
PTD parameter P1,Ti1 P2,Ti2 Switching frequency 1 Switching frequency 2 Feedback frequency Figure 7-22 PI Parameter 1. Generally, user does not need to adjust F06.00 - F06.05 parameters, so please pay enough attention when you decide to adjust these parameters. 2. While setting switching frequency, please note that switching frequency 1 (F06.04) must be lower than or equivalent to switching frequency 2 (F06.05). When there is overshoot with the speed, properly increase this parameter, if there is no overshoot, try to reduce this parameter and keep the factory setting.
168 Function Name of Function Code Parameter Description Unit Default Property Code Gain ASR P2 _ F06.03 Speed Integral Time Constant ASR T2 _ 0.000 - 30.000 0.000: No Integral s 0.300 ● F06.04 Switching Frequency 1 0.00 - Switching Frequency 2 Hz 5.00 ● F06.05 Switching Frequency 2 Switching Frequency 1 - Maximum Frequency F00.16 Hz 10.00 ● Function Name of Function Code Parameter Description Unit Default Property Code F06.06 Velocity Loop Anti-Saturation Factor 0.000 - 1.000 0.500 ●