sinee — 7.7 F06 Group: Vector Control Parameter

EM600 High-Performance Vector Control Inverter User Manual The velocity loop output filter can reduce the impacts upon current loop, but better not to set a large value for F06.07, which may cause slow response. Generally, user may use the defaults. If motor speed goes below the target value, increase the value set through F06.08. When inverter is in sensor vector control mode, this parameter is used to adjust speed stability accuracy of motor: if the accuracy is relatively lower, increase the value set by the parameter and vice versa. When inverter is in FVC control, this parameter can adjust output current of inverter under the same load.

This function code is used to set the action condition of torque limit during vector control. If inverter output torque is higher than the torque limit, torque limit function is enabled, so as to control output torque to be not higher than upper limit of speed control torque. F06.09=0 : F06.10 is Electric Torque (JOG). F06.11 is Brake Torque. F06.09=1/2/3/4 : torque limit is AI (pencentage) * F06.10/F06.11 F06.09=5 : torque limit is set by communication (Percentage).

169 Function Name of Function Code Parameter Description Unit Default Property Code F06.07 Time Constant of Output Filter of Velocity Loop 0.000 - 0.100 s 0.001 ● Function Name of Function Parameter Description Unit Default Property Code Code F06.08 Vector Control Slip Gain 10.00 - 200.00 % 100.00 ● Function Name of Function Code Parameter Description Unit Default Property Code F06.09 Speed Control Torque Lmit Source Selection 0: F06.10 and F06.11 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: Communication (Percentage) 6: Maximum of AI2 and AI3 7:

Minimum of AI2 and AI3 0 〇 F06.10 Upper Limit of JOG for Speed Control 0.0 - 250.0 % 165.0 ● F06.11 Upper Limit of Brake Torque for Speed Control 0.0 - 250.0 % 165.0 ●