sinee — 7.7 F06 Group: Vector Control Parameter

EM600 High-Performance Vector Control Inverter User Manual When inverter is in the vector control, add the voltage feedforward gain to realize the automatic torque boost, i.e., stator voltage drop compensation. Field Weakening Control Options of Synchronous Motor are described below. F06.21=0: Disabled If F06.21=0, field weakening control will not work. At this time, maximum value of motor rotation speed is related to bus voltage of inverter. When maximum speed of motor can not meet user requirements, user needs to start field weakening function of synchronous motor for field weakening speed rise. EM600 offers two field weakening modes: direct calculation mode and automatic adjustment mode.

F06.21=1 Direct Calculation In direct calculation method, required field weakening current is calculated as per target rotation speed and its size can be also adjusted manually through 06.22. The lower the field weakening current is, the lower the total output current will be, but this may not achieve the required field weakening effect. F06.21=2: Automatic Adjustment In automatic adjustment method, inverter will select optimum field weakening current automatically, but this may affect dynamic performance of the system or cause the system to be unstable.

Setting proportional gain (F06.24) and integral time (F06.25) can change the adjustment speed of field weakening current, but fast adjustment of field weakening current can result in instability. Generally, user does not need to make manual modification. 171 Function Name of Function Code Parameter Description Unit Default Property Code F06.20 Voltage Feedforward Gain 0 - 100 % 0 ● Function Name of Function Code Parameter Description Unit Default Property Code F06.21 Field Weakening Control Options 0: Disabled 1: Direct Calculation 2:

Automatic Adjustment 2 〇 F06.22 Field Weakening Voltage 70.00 - 200.00 % 95.00 ● F06.23 Maximum Field Weakening Current of Synchronous Motor 0.0 - 150.0 (100.0= Motor Rated Current) % 50.0 ● F06.24 Proportional Gain of Field Weakening Regulator 0.00 - 10.00 0.50 ● F06.25 Integral Time of Field Weakening Regulator 0.01 - 60.00 s 2.00 ● Function Name of Function Parameter Description Unit Default Property Code Code F06.27 Gain of Autotuning at Initial Position 0 - 600 % 80 ●