EM600 High-Performance Vector Control Inverter User Manual In PLC running mode, present speeds 1 – 15 can be used to set the running frequency, running direction, acceleration/deceleration time and running time. In the following part, preset speed 13 (being last preset speed) will be taken as an example. Its running applications are shown in Figure 7-26. If F08.12=50.00, the running frequency of preset speed 13 is 50.00Hz; If F08.43=31 , running direction controlled by preset speed 13 is reverse, with acceleration/deceleration controlled by acceleration/deceleration time 4 (F15.07/F15.08); If F08.44=5.0 , running time of preset speed 13 is 5.0s (default setting F08.18=0). 7.10 F09 Group:
PID Function Parameter EM600 inverter has a process PID function, which is to be described in this part. The process PID function is mainly used for pressure control, flow control and temperature control. 185 Function Name of Function Parameter Description Unit Default Property Code Code 1: Acceleration/Deceleration Time 2 2: Acceleration/Deceleration Time 3 3: Acceleration/Deceleration Time 4 F08.44 Running Time of Preset Speed 13 0.0 - 6000.0 5.0 ● F08.45 Setting of Preset Speed 14 Ones Place: Running Direction 0: Forward 1: Reverse Tens Place: Acceleration/Deceleration Time 0: Acceleration/Deceleration Time 1 1: Acceleration/Deceleration Time 2 2: Acceleration/Deceleration Time 3 3:
Acceleration/Deceleration Time 4 0 ● F08.46 Running Time of Preset Speed 14 0.0 - 6000.0 5.0 ● F08.47 Setting of Preset Speed 15 Ones Place: Running Direction 0: Forward 1: Reverse Tens Place: Acceleration/Deceleration Time 0: Acceleration/Deceleration Time 1 1: Acceleration/Deceleration Time 2 2: Acceleration/Deceleration Time 3 3: Acceleration/Deceleration Time 4 0 ● F08.48 Running Time of Preset Speed 15 0.0 - 6000.0 5.0 ●