sinee — 7.10 F09 Group: PID Function Parameter

EM600 High-Performance Vector Control Inverter User Manual Kp Ref + + Ts KpKi  Out + + d Figure 7-27 Process PID Block Diagram PID control is a closed loop control mode. Output signal (Out) of controlled object of the system is fed back to PID controller, which adjusts output of controller through PID arithmetic and forms a closed loop or multiple closed loops. By using PID control, output value and set target value of controlled object are consistent. See Figure 7-27 for the functional block diagram.

PID controller implements control by calculating controlled quantity with three calculation factors, i.e., P (proportional), I (integral) and D (differential) and on the basis of dispersion between target (Ref) and feedback signal. Features of various calculation factors are as follows: P (proportion): Proportional control is the simplest control mode. Output error signal and input error signal of its control are proportional. The system outputs the stable error when inverter is in proportional control only. I (integral): The integrals of output error signal and input error signal of the controller are directly proportional.

This control mode can eliminate stable error and enable the system to be free from stable error after entering the stable status. However, under this mode, inverter can not track intense changes. D (Differential): The differential values of output error signal and input error signal of the controller are directly proportional. Its controller can predicate the trend of error changes and respond to intense changes to improve the dynamic characteristics of the system in the regulation process. Fdb KpKdTs dt F09.00=0: Numeric PID Setting F09.01 PID setting is done by numeric PID setting, with the specific percentage of F09.01/F09.03 * 100.00%. F09.00=1:

AI1 186 Function Name of Function Parameter Description Unit Default Property Code Code F09.00 PID Setting Source 0: Numeric PID Setting 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse (X7) 6: Communication Setting 0 〇 F09.01 Numeric PID Setting 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.03 PID Setting Feedback Range 0.1 - 6000.0 100.0 ●