EM600 High-Performance Vector Control Inverter User Manual F09.00=2: AI2 F09.00=3 : AI3 F09.00=4: AI4 (Expansion Card) The specific percentage of PID setting is directly determined by AI (percentage). F09.00=5: High-Frequency Pulse (X7) Specific percentage of PID setting is directly determined by HDI (percentage). Please refer to the description of F00.04 for detailed explanations of AI1-AI4 and X7. When they are used for PID setting, their percentages are set values, with maximum output of 100.00%. F09.00=6: Communication Setting The specific percentage of PID setting is directly determined by communication (percentage).
If inverter is under master-slave communication control (F10.05=1) and present inverter is a slave (F10.06=0), set percentage is “700 FH (Master-Slave Communication Setting) * F10.08 (Receiving Proportionality Factor of Slave)”. Range of 700 FH is -100.00% to 100.00%. See Table 12-2 for details. For general communication (F10.05=0), set percentage is “7004H (Communication Setting of Process PID)”. Range of 7004H is -100.00% to 100.00%. See Table 12-2 for details. F09.02=1: AI1 F09.02=2: AI2 F09.02=3: AI3 F09.02=4: AI4 (Expansion Card) The specific percentage of PID feedback is directly determined by AI (percentage). F09.02=5:
High-Frequency Pulse (X7) The specific percentage of PID feedback is directly determined by HDI (percentage). Please refer to the description of F00.04 for detailed explanations of AI1-AI4 and X7. When they are used for PID setting, their percentages are set values, with maximum output of 100.00%. F09.02=6: Communication Setting The specific percentage of PID feedback is directly determined by communication (percentage). If inverter is under master-slave communication control (F10.05=1) and present inverter is a slave (F10.06=0), the feedback percentage is “700 FH (Master-Slave Communication Setting) * F10.08 (Receiving Proportionality Factor of Slave)”.
Range of 700 FH is -100.00% to 100.00%. See Table 12-2 for details. For general communication (F10.05=0), the feedback percentage is “7005 H (Communication Setting of Process PID Feedback)”. Range of 7005 H is -100.00% to 100.00%. See Table 12-2 for details. 187 Function Name of Function Parameter Description Unit Default Property Code Code F09.02 PID Feedback Source 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse (X7) 6: Communication Setting 1 〇