sinee — 7.10 F09 Group: PID Function Parameter

EM600 High-Performance Vector Control Inverter User Manual The action mode of process PID is determined through setting of F09.04 and the status of input function “PID Positve/Negative Action Switch” together. See Table 7-12 for their relationship details. Table 7-12 PID Positive/Negative Action Note: The offset is usually “Setting - Feedback” in PID control.  When feedback signal is greater than PID setting, it’s required to drop inverter output frequency to balance PID. An example is given about supply control:

when the pressure increases, the pressure feedback increases as well; at this time, only by reducing output frequency of inverter can the pressure go down and stabilize; PID setting shall be in the positive action control.  When feedback signal is greater than PID setting, it’s required to increase inverter output frequency to balance PID. An example is given about supply control: PID regulator shall be in the negative action control. To meet different complicated applications, process PID module has introduced two groups of PID parameters. Parameters can be switched between these two groups through the function setting of F09.11 and the input applications (input function “43:

PID Parameter 188 Function Code Name of Function Code Parameter Description Uni t Default Property F09.04 PID Positive/Negative Reaction 0: Positive Action 1: Negative Action 0 〇 F09.04 PID Positive/Negative Action Mode Description Reaction 0 0 Positive Action Positive offset and output quantity 0 1 Negative Action Positive offset, but negative output quantity 1 0 Negative Action Positive offset, but negative output quantity 1 1 Positive Action Positive offset and output quantity Function Name of Function Parameter Description Unit Default Property Code Code F09.05 Proportional Gain 1 0.00 - 100.00 0.40 ● F09.06 Integral Time 1 0.000 - 30.000, 0.000:

No Integral s 10.000 ● F09.07 Differential Time 1 0.000 - 30.000 ms 0.000 ● F09.08 Proportional Gain 2 0.00 - 100.00 0.40 ● F09.09 Integral Time 2 0.000 - 30.000, 0.000: No Integral s 10.000 ● F09.10 Differential Time 2 0.000 - 30.000 ms 0.000 ● F09.11 PID Parameter Switching 0: Disabled 1: Switching through Numeric Input Terminal 2: Automatic Switching by Offset 0 ● F09.12 PID Parameter Switching Offset 1 0.00 - F09.13 % 20.00 ● F09.13 PID Parameter Switching Offset 2 F09.12 - 100.00 % 80.00 ●