sinee — 7.10 F09 Group: PID Function Parameter

EM600 High-Performance Vector Control Inverter User Manual Switching”, offset e (k), etc.) and performed for linear interpolation. See Table 7-13 for details. Table 7-13 PID Parameter Options As listed in the table above, when function code F09.11 is set as 0, PID parameters will not be switched and the first group of parametes works; when function code is set as 1, PID parameters will be switched according to input function “43: PID Parameter Switching”; when function code is set as 2, PID parameters will be selected or operated by linear interpolation according to the relationship between absolute value of present offset e(k) (=|Setting - Feedback|) and function codes F09.12 and F09.13.

When F09.12≤|e(k)|≤F09.13, present PID parameter is obtained through the linear interpolation of parameters of the frist group and the second group. See 7-28 median section for specific principles. PID Parameter Parameter 1 2 2 ( , ) e Y Parameter 2 1 1 ( , ) e Y | Offset | 100.00% 0 Switching Offset 1 Switching Offset 2 Figure 7-28 Automatic Switching of PID Parameters by Offset (F19.11=2) The process PID module outputs PID initial value (F09.14) constantly for PID initial value retention time after inverter starts to run; afterwards, inverter proceeds with PID output regulation. See Figure 7-29 for specific effects.

When PID initial value is held for 0.00s, i.e., F09.15=0.00, the output function of PID initial value is disabled. 189 Mode Description F09.11 Other Conditions 0 -- Not Switching of PID Parameter, the first group of parameters work 43: PID Parameter PID parameter is switched by the numeric input terminal Switch (43: PID Parameter Switch) 1 0 Invalid switching, the first group of parameters work 1 Invalid switching, the second group of parameters work |e (k)| - F09.12/13 2:

Automatic Switching by Offset |e (k)| The first group of parameters 2 |e (k)|> F09.13 The first group of parameters Intermediate Value Two groups of parameters are taken as the reference for linear interpolation according to the offset. Function Name of Function Code Parameter Unit Default Property Code Description F09.14 PID Initial Value 0.00 - 100.00 % 0.00 ● F09.15 PID Initial Value Retention time 0.00 - 650.00 s 0.00 ●