EM600 High-Performance Vector Control Inverter User Manual Output Frequency PID Initial Value F09.14 t 0 Figure 7-29 PID Initial Value Output PID Initial Value Holding Time F09.15 For PID output limit, the output range of the whole process PID module is F09.17 - F09.16, actual regulation results are in this scope, with the output at the boundary. When the offset between PID setting and feedback is less than and equal to the offset limit (F09.18), PID stops the regulation. In this way, when the offset between setting and the feedback is low, output frequency stabilizes, which works for some closed loop control occasions. When input terminal function “41:
Process PID Stop” is enabled, PID can also stop the regulation. User may use these two methods together. Differential (D) component of PID regulator can not be greater than PID differential limit value (F09.19) to avoid excessively high offset, otherwise the output is also greater and causes the system oscillation. Properly setting this value can affect the impact of occasional interference upon the system. To perform PID regulation in a faster and better way, it's not required to conduct integral regulation temporarily sometimes, but only PD or P regulation. EM600 inverter has a particular integral separation function:
When the offset between PID setting and feedback is 190 Function Code Name of Function Code Parameter Description Un it Default Property F09.16 Upper Limit of PID Output F9.17 - +100.0 % 100.0 ● F09.17 Lower Limit of PID Output –100.0 - F9.16 % 0.0 ● Function Name of Function Code Parameter Description Unit Default Property Code F09.18 PID Offset Limit 0.00 - 100.00, Disabled at 0.00 % 0.00 ● Function Code Name of Function Code Parameter Description Un it Default Property F09.19 PID Differential Limit 0.00 - 100.00 % 5.00 ● Function Code Name of Function Code Parameter Description Unit D efault Property F09.20 PID Integral Separation Threshold 0.00 - 100.00, (100.00%=Integral Separation Disabled) % 100.00 ●