EM600 High-Performance Vector Control Inverter User Manual greater than PID integral separation threshold (F09.20), the integral separation is enabled, i.e., integral (I) regulation function of PID regulator stops. Input terminal function “42: Process PID Integral Stop” can be used together for remote control. If function code setting is disabled (F09.20=100.00), input terminal function does not work. See Table 7-14 for details. Table 7-14 Integral Separation Function Description PID setting variation time refers to the time required for the change from 0.0% to 100.0%. It is similar to an acceleration/deceleration function.
If PID setting changes, actual setting value of PID will have a linear change to reduce impact incurred upon system. After intial value is set, smooth setting will be invalid. F09.22 is used for filtering of PID feedback quantity. Filtering action is in favor of reducing interference impact upon feedback quantity, but causes reponse performance of closed loop system of the process to go down. F09.22 is used for filtering of PID output quantity. Fltering action will weaken sudden change of inverter output frequency, but will also cause the response performance of closed loop system of the process to go down.
PID feedbck disconnection detection function can be used to prevent a slip accident due to the feedback disconnection. The setting depends upon the nature of feedback sensor. If 0.0% sensor is fed back at disconnection, it’s required to set F09.25 as a proper value. When feedback quantity is less than the value set through F09.25 and this status is maintained for F09.26, it is deemed as PID feedback disconnection. If 100.0% sensor is fed back at disconnection, it’s required to set F09.24 as a proper value. When feedback quantity 191 Mode Description F09.20 DI (42) F09.20: PID Integral Separation Threshold; DI (42):
Process PID Integral Stop 100.00% -- The integral (I) is always enabled 0.00% - 99.99% Up to the relationship between |e (k)| and F09.20, and the status of DI Disabled If |e (k)| >F09.20, the integral separation will be enabled.
Enabled Integral Separation Enabled Function Code Name of Function Code Parameter Description Unit Default Property F09.21 PID Setting Variation Time 0.000 - 30.000 s 0.000 ● Function Code Name of Function Code Parameter Description Unit Default Property F09.22 PID Feedback Filter Time 0.000 - 30.000 s 0.000 ● F09.23 PID Output Filter Time 0.000 - 30.000 s 0.000 ● Function Name of Function Code Parameter Description Unit Default Property Code F09.24 Upper Limit Detection Value of PID Feedback Disconnection 0.00 - 100.00 100.00.00=Feedback Disconnection Disabled % 100.00 ● F09.25 Lower Limit Detection Value of PID Feedback Disconnection 0.00 - 100.00 0.00=Feedback Disconnection Disabled % 0.00 ● F09.26 PID Feedback Disconnection Detection Time 0.000 - 30.000 s 0.000 ●