sinee — 7.10 F09 Group: PID Function Parameter

EM600 High-Performance Vector Control Inverter User Manual is greater than the value set through F09.24 and this status is maintained for F09.26, it is deemed as PID feedback disconnection. ★ Once feedback sensor is determined, only corresponding detection mode is enabled, either upper limit detection or lower limit detection, other than both.

At a moment in some occasions, when both output quantity and feedback quantity stabilize or controlled quantity is in permitted range, output is not permitted at this time and inverter can enter into transient sleep status; when controlled quantity exceeds permitted range, inverter is awakened and starts output again; in this way, these function codes not only control controlled quantity within permitted quantity and saves energy. See Table 7-15 for detailed function description. Table 7-15 Sleep Awakening Function 192 Function Name of Function Code Parameter Description Unit Default Property Code F09.27 PID Sleep Control 0: Disable 1: Zero Speed Enable 2: Lower Limit Frequency Enable 3:

No Output Enable 0 ● F09.28 Sleep Action Point 0.00 - 100.00 (100.00 corresponds to PID Setting Feedback Range ) % 100.00 ● F09.29 Sleep Delay Time 0.0 - 6500.0 s 0.0 ● F09.30 Awakening Action Point 0.00 - 100.00 (100.00 corresponds to PID Setting Feedback Range ) % 0.00 ● F09.31 Awakening Delay Time 0.0 - 6500.0 S 0.0 ● Mode Action Status Description Mode Positive Action (Constant Voltage Control) Normal Operation Judge sleep condition:

If absolute value of feedback > sleep action point (F09.28) or inverter output frequency reachs the lower limit and cannot continue to decelerate (inverter lower limit frequency or PID output lower limit) and this status is maintained for sleep delay time (F09.29), inverter enters into sleep mode. ★ During delay, PID continues the output; after delay, PID outputs 0. Sleep Mode Judge awakening condition: If absolute value of feedback Negative Action (Constant Temperature Control) Normal Operation Judge sleep condition: If absolute value of feedback