sinee — 7.11 F10 Group: Communication Function Parameter

EM600 High-Performance Vector Control Inverter User Manual Recommendation: during positive action, F09.28 (awakening action point) ≥ F09.30 (awakening action point); during negative action, F09.28 (awakening action point) ≤ F09.30 (awakening action point). These function codes are used for PID setting together with function code F09.00. EM600 inverter has preset PID setting function, for which switching condition is mainly determined by input function “15: Preset PID Terminal 1” and “16: Preset PID Terminal 2”. See Table 7-16 for details. Table 7-16 Preset PID Setting Function 7.11 F10 Group:

Communication Function Parameter EM 600 inverter supports Modbus protocol of RTU format and the single-master and multi-slave communication network with RS485 bus (see 11.5). 193 Mode Action Status Description Mode outputs 0. Sleep Mode Judge awakening condition: If absolute value of feedback >= awakening action point (F09.28) and this status is maintained for awakening delay time (F09.31), inverter exits sleep mode. ★ During delay, PID outputs 0; after delay, PID continues with normal output.

Function Name of Function Code Parameter Description Unit Default Property Code F09.32 Preset PID Setting 1 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.33 Preset PID Setting 2 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.34 Preset PID Setting 3 0.0 – PID Setting Feedback Range F09.03 0.0 ● Mode Setting Range PID Setting 16 15 F09.00 Disabled Disabled 0 F09.01 0.0 - F09.03 0.00% - 100.00% 1 AI1 -100.00% - 100.00% -100.00% - 100.00% 2 AI2 -100.00% - 100.00% -100.00% - 100.00% 3 AI3 -100.00% - 100.00% -100.00% - 100.00% 4 AI4 -100.00% - 100.00% -100.00% - 100.00% 5 HDI -100.00% - 100.00% -100.00% - 100.00% 6 485 -100.00% - 100.00% -100.00% - 100.00% Disabled Enabled -- F09.32 0.0 - F09.03 0.00% - 100.00% Enabled Disabled -- F09.33 0.0 - F09.03 0.00% - 100.00% Enabled Enabled -- F09.34 0.0 - F09.03 0.00% - 100.00% Function Code Name of Function Parameter Description Unit Default Property Code F10.00 I nverter Address 1 - 247, 0 as broadcasting address 1 〇