EM600 High-Performance Vector Control Inverter User Manual As a slave when connected to the whole communication network, inverter must have a unique address, for which setting scope is 1 to 247. That is to say, 247 inverters are supported by one network. ★ 0 is a broadcasting address, which can be recognized by all inverters and does not need to be set specifically. All masters and slaves connected to the same network must follow the same transmission principles (for example same bit rate, data format and protocol format) to ensure normal communication. Therefore, settings for F10.01 (bit rate), F10.02 (data format) and F10.10 (communication protocol; default:
Modbus-RTU protocol for EM600) for all devices connected to the network are the same. EM600 Inverter supports 6 bit rates (unit: bit/s) when it is in Modbus-RTU communication. If F10.01=9600 bps, it means that 9600 bits will be transmitted for each second. Under default applications, to transmit each byte of valid data (for example 0x01), actual transmission is 10 bits and the time needed is about 1.04 ms (about 1.04167 ms=10bit/9600 bps). When transmitting data via Modbus protocol of RTU format, inverter supports 6 different data formats according to data combinations.
When transmitting data via Modbus protocol of RTU format, inverter supports 6 different data formats according to data combinations. If F10.02=0, it means that present data format is 1 start bit + 8 data bits + no parity +1 stop bit ★ N (NONE), no parity; E (EVEN), even parity; O (ODD), odd parity. Inverter also supports communication overtime and response delay, when it is networked for communication with Modbus protocol, in order to meet various requirements. 194 Function Code Name of Function Code Parameter Description Unit Default Property F10.01 Modbus Communication Bit Rate 0: 4800 1: 9600 2: 19200 3: 38400 4: 57600 5:
115200 bps 1 〇 Function Name of Parameter Description Unit Default Property Code Function Code F10.02 Modbus Data Format 0: 1-8-N-1 (1 start bit + 8 data bits +1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity + 1 stop bit) 2: 1-8-O-1 (1 start bit + 8 data bits + 1 odd parity + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits +2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity +2 stop bits) 5: 1-8-O-2 (1 start bit + 8 data bits + 1 odd parity +2 stop bit) 0 〇 Start bit Valid data Parit y Stop bit 1 7 6 5 4 3 2 1 0 N/O/E 1