EM600 High-Performance Vector Control Inverter User Manual t w3 t t s t w1 t w2 tr Figure 7-31 Complete Data Frame Time Sequence Learning EM600 supports master-slave communication function. In master-slave communication, one inverter is used as master while other inverters are slaves; all slaves work as the command sent by master to achive the synchronous running function of multiple inverters. For master, inverter will be set as follows: Set F10.05=1 to enable master-slave function; Set F10.06=1 to set present inverter as master (only one inverter can be used as master in a network); F10.07 is used to set the variable needing synchronization; for example output current, set F10.07=5.
For a slave, inverter will be set as follows: Set F10.05=1 to enable master-slave function; Set F10.06=0 to select present inverter as a slave; Set a setting as communication setting; for example, if F09.00=6, and process PID is set individually (F00.05=10 and F00.06=1), slave inverter will take output current of master as setting for PID regulation. For a slave, F10.08 can be used to determine how inverter makes use of received data. If F10.08=0.80, finally used data is “Recv (Received Data) * 0.80 (F10.08)”. For master, F10.09 can be used to determine how long a command is sent by master.
196 Function Name of Function Code Parameter Description Unit Default Property Code F10.05 Master-Slave Communication Function 0: Disabled 1: Enabled 0 〇 F10.06 Master-Slave Options 0: Slave 1: Master (Sent by Broadcast) 0 〇 F10.07 Data Sent by Master 0: Output Frequency 1: Set Frequency 2: Output Torque 3: Set Torque 4: PID Setting 5: Output Current 1 〇 F10.08 Receiving Proportionality Factor of Slave 0.00 - 10.00 (Times) 1.00 ● F10.09 Sending Interval of Master 0.000 - 30.000 s 0.200 ● Function Code Name of Function Code Parameter Description Unit Defaul t Property F10.10 Communication Protocol 0: Modbus-RTU Protocol 1: Profibus-DP Protocol 0 〇