EM600 High-Performance Vector Control Inverter User Manual F10.17 - F10.31 are used to define data sent from communication expansion card (i.e., received by inverter) and are generally parameter settings; F10.32 - F10.46 are used to define data received by communication expansion card (sent by inverter) and are generally status parameters. All the exchange data shall correspond to these functions codes or the defined fileds of virtual addresses and not be manually set. Refer to communication expansion card instructions.
All the exchange data correspond to function codes or virtual 198 Function Name of Function Code Parameter Description Unit Default Property Code F10.17 Received Data Type PZD2 When the displayed data is 65535, it means that present PZD is not used.
When the displayed data is other data, for example 4609, it means that the function parameter is F18.01 (18D=12H, 01D=01H, 1201H=4609D) 65535 〇 F10.18 Received Data Type PZD3 65535 〇 F10.19 Received Data Type PZD4 65535 〇 F10.20 Received Data Type PZD5 65535 〇 F10.21 Received Data Type PZD6 65535 〇 F10.22 Received Data Type PZD7 65535 〇 F10.23 Received Data Type PZD8 65535 〇 F10.24 Received Data Type PZD9 65535 〇 F10.25 Received Data Type PZD10 65535 〇 F10.26 Received Data Type PZD11 65535 〇 F10.27 Received Data Type PZD12 65535 〇 F10.28 Received Data Type PZD13 65535 〇 F10.29 Received Data Type PZD14 65535 〇 F10.30 Received Data Type PZD15 65535 〇 F10.31 Received Data Type PZD16 65535 〇 F10.32 Sent Data Type PZD2 65535 〇 F10.33 Sent Data Type PZD3 65535 〇 F10.34 Sent Data Type PZD4 65535 〇 F10.35 Sent Data Type PZD5 65535 〇 F10.36 Sent Data Type PZD6 65535 〇 F10.37 Sent Data Type PZD7 65535 〇 F10.38 Sent Data Type PZD8 65535 〇 F10.39 Sent Data Type PZD9 65535 〇 F10.40 Sent Data Type PZD10 65535 〇 F10.41 Sent Data Type PZD11 65535 〇 F10.42 Sent Data Type PZD12 65535 〇 F10.43 Sent Data Type PZD13 65535 〇 F10.44 Sent Data Type PZD14 65535 〇 F10.45 Sent Data Type PZD15 65535 〇 F10.46 Sent Data Type PZD16 65535 〇