sinee — 7.11 F10 Group: Communication Function Parameter

EM600 High-Performance Vector Control Inverter User Manual address definition areas respectively (refer to Communication Protocol) and user does not need to set them manually. Refer to corresponding manuals of communication expansion cards. Communication card only read the parameters. Refer to corresponding manuals of communication expansion cards. Communication card only read the parameters. 199 Function Name of Function Parameter Description Unit Default Property Code Code F10.47 Communication Card Status Ones Place: Profibus-DP 0: Initialization Status 1: Wait for Parameterization Status 2: Wait for Configuration Status 3: Data Exchange Status 4: Modbus Communication Fault Status 5:

Factory Test Status Place: CANopen 0: Initialization Status 1: Pre-Operation Status 2: Operation Status 3: Stop Status 4: CANopen Communication Fault Status 5: Modbus Communication Fault Status 6: Factory Test Status Hundreds Place: DeviceNet 0: Initialization Status 1: MACID Detection Status 2: Online Non-Connection Status 3: Connection Status 4: IO Communication Overtime Status 5: DeviceNet Bus Communication Fault Status 6: Modbus Communication Fault Status 7:

Factory Test Status 000 × Function Code Name of Function Code Parameter Description Unit Default Property F10.48 Communication Card Software Version × Function Code Name of Function Code Parameter Description Unit Default Property F10.49 number of process data 1~16 2 ●