EM600 High-Performance Vector Control Inverter User Manual F13.01= 0: Numeric Torque Setting F13.02 Torque is set through F13.02. F13.01=1: AI1 F13.01=2: AI2 F13.01=3 : AI3 F13.01=4: AI4 (Expansion Card) Torque is controlled by AI (percentage) * F13.02. F13.01=5: High-Frequency Pulse Input (X7) Torque is controlled by HDI (percentage) * F13.02. Please refer to the description of F00.04 for detailed explanations of AI1-AI4 and X7. F00.04 has the same meanings as AI1-AI4 and X7. 100.00% is the percentage inputted through F13.02 (Numeric Torque Setting). F13.01=6: Communication Setting Torque is determined by communication, etc.
If inverter is under master-slave communication control (F10.05=1) and present inverter is a slave (F10.06=0), set percentage is “700FH (Master-Slave Communication Setting) * F10.08 (Receiving Proportionality Factor of Slave)”. Range of 700FH is -100.00% to 100.00%. See Table 12-2 for details. For general communication (F10.05=0), set percentage is “7003H (Torque Communication Setting) * F00.18 (Numeric Torque Setting)”. Range of 7003H is -200.00% to 200.00%. See Table 12-2 for details. 209 29: Torque Control 28:
Switch between Speed Final Control F13.00 F13.00 Disabled Control and Torque Control Mode Enabled * * Speed Control Disabled Enabled 0 Torque Control 1 Speed Control Disabled 0 Speed Control 1 Torque Control Function Name of Parameter Description Unit Default Property Code Function Code F13.01 0: Numeric Torque Setting F13.02 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse Input (X7) 6: Communication Setting (Full ranges of options 1 to 6 correspond to numeric torque setting F13.02) 0 〇 F13.02 Numeric Torque Setting -200.0 - 200.0 (100.0= Motor Rated Torque) % 100.0 ●