EM600 High-Performance Vector Control Inverter User Manual To realize the diversification of torque application, EM600 inverter supports preset torque function. Set input terminal “17: Preset Torque Terminal 1” and “18: Preset Torque Terminal 2” See Table 7-19 for details. Table 7-19 Preset Torque Commands and Preset Torque Terminals Setting F13.06 can make the motor speed change smoothly. The value set by F13.06 refers to the time that torque current increases from 0 to rated torque current or decreases from rated current to 0. F13.08=0: Set through F13.09 Under torque control mode, upper limit frequency is set through F13.09.
210 Function Name of Parameter Description Unit Default Property Code Function Code F13.03 Preset Torque 1 -200.0 - 200.0 % 0.0 ● F13.04 Preset Torque 2 -200.0 - 200.0 % 0.0 ● F13.05 Preset Torque 3 -200.0 - 200.0 % 0.0 ● 18: Preset Torque 17:
Preset Torque Torque Number Torque Setting Terminal 2 Terminal 1 Disabled Disabled Preset Torque 1 Set through F13.01 Disabled Enabled Preset Torque 2 F13.03 F13.03 Enabled Disabled Preset Torque 3 F13.04 F13.04 Enabled Enabled Preset Torque 4 F13.05 F13.05 Function Name of Function Code Parameter Description Unit Default Property Code F13.06 Torque Control Acceleration/Deceleration Time 0.00 - 120.00 s 0.00 ● Function Name of Function Code Parameter Description Unit Default Property Code F13.08 Upper Limit Frequency of Torque Control 0: Set through F13.09 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse Input (X7) 6: Communication Percentage Setting 7:
Communication Direct Setting 0 〇 F13.09 Upper Limit Frequency of Torque Control 0.00 - Maximum Frequency F00.16 Hz 50.00 ● F13.10 Upper Limit Frequency Offset 0.00 - Maximum Frequency F00.16 Hz 0.00 ● F13.18 Reverse speed limit selection 0 - 100 % 100 ● F13.19 Torque Control Speed Priority Selection 0: Disabled 1: Enabled 0 ●