EM600 High-Performance Vector Control Inverter User Manual As for normal running (non jog running), the system offers 4 groups of acceleration/deceleration time options (first group F00.14 and F00.15) to meet different demands. After setting, user can switch between numeric input modes “19: Acceleration/Deceleration Time Terminal 1” and “20: Acceleration/Deceleration Time Terminal 2”. See Table 7–4 Numeric Multi-Function Input Terminals.
Output Frequency Acceleration/ Deceleration Time Reference Frequency Set Frequency F15.09 0 Actual Acceleration Time Actual Deceleration Time t Figure 7-33 Acceleration/Deceleration Time As indicated in Figure 7-33, defined acceleration time refers to the time that frequency increases from 0.00 Hz to acceleration/deceleration time reference frequency; deceleration time refers to the time that frequency decreases from acceleration/deceleration time reference frequency to 0.00 Hz. Actual acceleration/deceleration time depends upon the ratio of set frequency to reference frequency. F15.09 is used to set acceleration/deceleration time reference frequency.
If F15.09=0, reference frequency is set by F00.16 (maximum frequency). If also F00.16=100.00 Hz, acceleration time refers to the time that output frequency increases from 0.00 Hz (100.00 Hz) to 100.00 Hz (0.00 Hz), and deceleration time refers to the time that output frequency decreases from 100.00 Hz (0.00 Hz) to 0.00 Hz (100.00 Hz).
Set Deceleration Time Set Acceleration Time 214 Function Name of Function Parameter Description Unit Default Property Code Code F15.06 Deceleration Time 3 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.07 Acceleration Time 4 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.08 Deceleration Time 4 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.09 Acceleration/Decelerat on Time Reference Frequency i 0: Maximum Frequency F00.16 1:
50 Hz 0 〇 Function Parameter Name of Function Code Un it Default Property Code Description F15.10 Automatic Switching between Acceleration and Deceleration Time 0: Disabled 1: Enabled 0 〇 F15.11 Switching Frequency between Acceleration Time 1 and Acceleration Time 2 0.00 - Maximum Frequency F00.16 Hz 0.00 ●