sinee — 7.16 F15 Group: Auxiliary Function

EM600 High-Performance Vector Control Inverter User Manual If inverter runs at a common (other than PLC, PID, etc.) speed (other than torque, etc.) of motor 1 and acceleration and deceleration time terminals (19: Acceleration/Deceleration Time Terminal 1, 19: Acceleration/Deceleration Time Terminal 1) are disabled, inverter can complete automatic switching between the two terminals by setting F15.10 as 1. See Figure 7-34 for details.

Output Frequency Switching Frequency between Acceleration Time 1 and Acceleration Time 2 Switching Frequency between F15.11 Acceleration Time 1 and Acceleration Time 2 F15.12 0 Acceleration Time 1 F00.14 Acceleration Time 2 F13.03 Deceleration Time 2 F13.04 Deceleration Time 1 F00.15 t Figure 7-34 Automatic Switching between Acceleration Time and Deceleration Time In acceleration, if output frequency is less than F15.11, then acceleration time 1 is present acceleration time, otherwise, acceleration time 2 is present acceleration time.

In deceleration, if output frequency is less than F15.12, then deceleration time 1 is present deceleration time, otherwise, deceleration time 2 is present deceleration time. Probably, acceleration/deceleration time can be a large figure depending upon different applications. The system offers 3 kinds of acceleration/deceleration time units, which are set through F15.13. If F15.13=1, it means that acceleration/deceleration time unit is “0.1 s”. Except F13.06 (Torque Control Acceleration/Deceleration Time) others acceleration and deceleration time will be changed. For example, in default conditions the value of F00.14 will change from 15.00s to 150.0s.

215 F15.12 Switching Frequency between Acceleration Time 1 and Acceleration Time 2 0.00 - Maximum Frequency F00.16 Hz 0.00 ● Function Parameter Name of Function Code Unit Default Property Code Description F15.13 Acceleration/Deceleration Time Unit 0:0.01s 1:0.1s 2:1s 0 〇 Function Parameter Name of Function Code Unit Default Property Code Description F15.14 Hopping Frequency Point 1 0.00 - 600.00 Hz 600.00 ● F15.15 Frequency Hopping Range 1 0.00 - 20.00 Disabled at 0.00 Hz 0.00 ● F15.16 Hopping Frequency Point 2 0.00 - 600.00 Hz 600.00 ● F15.17 Frequency Hopping Range 2 0.00 - 20.00 Disabled at 0.00 Hz 0.00 ● F15.18 Hopping Frequency Point 3 0.00 - 600.00 Hz 600.00 ● F15.19 Frequency Hopping Range 3 0.00 - 20.00 Disabled at 0.00 Hz 0.00 ●