EM600 High-Performance Vector Control Inverter User Manual Hopping frequency function enables inverter output frequency to avoid mechanical resonance with mechanical laod. Inverter is not permitted to run at a constant speed in hopping frequency range, but in acceleration process, there is no hopping and inverter runs smoothly. Set Frequency Hopping Frequency Frequency Hopping Range 3 Point 3 Frequency Hopping Range 2 Hopping Frequency Hopping Frequency Point 2 Frequency Hopping Range 1 Point 1 t Figure 7-35 Frequency Hopping As indicated in Figure 7-35, frequency hopping function is set through “Hopping Frequency Point+Frequency Hopping Range”. Specific frequency hopping is:
Hopping Frequency Point-Frequency Hopping Range, Hopping Frequency Point+Frequency Hopping Range. Up to three frequency hopping ranges can be set. When their hopping ranges are all set as 0, corresponding frequency function is disabled. When frequency hopping function is enabled and if set frequency is in frequency hopping range, then finally set frequency will be “Hopping Frequency Point-Frequency Hopping Range” during rising of set frequency or will be “Hopping Frequency Point+Frequency Hopping Range” during decreasing of set frequency.
Different frequency hopping ranges can be superposed (see frequency hopping ranges 1 and 2 in Figure 7-35) and final frequency hopping range is (Hopping Frequency Point 1-Frequency Hopping Range 1, Hopping Frequency Point 2+Frequency Hopping Range 2). Output Frequency Set Frequency Set Frequency + Range Set Frequency – Range 0 Output Terminal t Disabled 0 t Figure 7-36 FAR Detection 216 Function Name of Function Code Parameter Unit Default Property Code Description F15.20 FAR Detection Bandwidth 0.00 - 50.00 Hz 2.50 〇 Disabled En Enabled able