sinee — 7.16 F15 Group: Auxiliary Function

EM600 High-Performance Vector Control Inverter User Manual As indicated in Figure 7-36, when multi-function output terminal or relay output is set as “2: FAR”, if absolute value of the difference between output frequency and set input frequency is less than or equal to FAR (F15.20) during inverter running (non-autotuning), multi-function output terminal outputs active level, otherwise multi-function output terminal outputs inactive level. Figure 7-37 FDT Detection As indicated in Figure 7-37, when multi-function output terminal or relay output is set as “3: Output Frequency Detection Range FDT1” or “4:

Output Frequency Detection Range FDT2”, if absolute value of output frequency is greater than output frequency detection range FDT1/2 (F15.21/F15.23), corresponding function terminal outputs active level during inverter running; if absolute value of output frequency drops to a value less than or equal to “Output Frequency Detection Range FDT1/2 (F15.21/F15.23) - FDT1/2 hysteresis”, corresponding function terminal outputs inactive level; if absolute value of output frequency falls between “Output Frequency Detection Range - Hysteresis” and “Output Frequency Detection Range”, output level of corresponding function terminal remains the same.

217 Function Name of Function Code Parameter Description Unit Default Property Code F15.21 Output Frequency Detection Range FDT1 0.00 - Maximum Frequency F00.16 Hz 30.00 〇 F15.22 FDT1 Hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 〇 F15.23 Output Frequency Detection Range FDT2 0.00 - Maximum Frequency F00.16 Hz 20.00 〇 F15.24 FDT2 Hysteresis -(Fmax-F15.23)~F15.23 Hz 2.00 〇 Function Code Name of Function Parameter Description Unit Default Property Code F15.25 Analog Quantity Level Detection ADT 0: AI1 1: AI2 2: AI3 0 ○