sinee — 7.16 F15 Group: Auxiliary Function

EM600 High-Performance Vector Control Inverter User Manual to brake of large inertia or occasions requiring rapid brake and stop. User needs to choose proper braking resistor and braking unit. See 11.1 Braking Resistor and 11.2 Braking Unit. Figure 7-39 Energy Consumption Brake As indicated in Figure 7-39, when energy consumption brake is enabled (F15.30=1) and bus voltage is greater than operation voltage of energy consumption brake (F15.31), energy consumption brake starts; when bus voltage drops to a value below a certain value, energy consumption brake is disabled.

When inverter is in energy consumption brake, IGBT in braking unit is on and energy can be discharged rapidly through braking resistor. Brake duty ratio (F15.32) describes duty ratio when IGBT is on. The higher duty ratio is, the higher the brake level will be. When set frequency of inverter is lower than lower limit frequency (F00.19), control mode can be set through F15.33. Three fan control modes are available to reasonably use fan. It is controlled through F15.34. See Table 7-21 for control modes of fan. Table 7-21 Fan Running 219 Function Code Name of Function Code Parameter Description Unit Default Property F15.33 Control Mode of Set Frequency Lower Than Lower Limit Frequency 0:

Run at Lower Limit Frequency 1: Stop 0 〇 Function Name of Function Code Parameter Description Unit Default Property Code F15.34 Fan Control 0: Run at Energization 1: Run at Start 2: Run at Intelligent Temperature Control 1 〇 Fan Control Description 0: Run at Energization Fan runs immediately after inverter is powered on. 1: Run at Start Fan starts running after inverter starts running; fan stops running 1 minute after inverter enters parameter setting status. 2: Run at Intelligent Temperature Control When inverter temperature > 45℃, fan starts running; when inverter temperature