sinee — 7.16 F15 Group: Auxiliary Function

EM600 High-Performance Vector Control Inverter User Manual ★ If “2: Run at Intelligent Temperature Control” is selected, make sure that inverter temperature detection module works normally. When input voltage of inverter is lower than output frequency, user can increase overmodulation intensity to enhance utilization factor of bus voltage and increase upper limit of output voltage. If F15.35=1.10, upper voltage limit can be increased by up to 10%, output current at heavy load may be reduced, but current harmonic will go up.

For PWM modulation method, if F15.36=0, the 7 preset PWM modulation always applies; if F15.36=1, the 7 preset PWM modulation applies when output frequency is lower than switching frequency (F15.37), or the 5 present PWM modulation applies when output frequency is greater than switching frequency, In comparison with the 5 preset PWM modulation mode, current ripple wave for the 7 preset PWM modulation mode is smaller, but switching loss is higher, and inverter would have a higher heating level and a higher temperature rise. User does not need to change the option of this function code.

Only when there are special requirements on output voltage waveform quality or motor is in an abnormal status (for example oscillation) will user try to select a different compensation mode. Generally, compensation mode 1 is selected, but user may select compensation mode 2 in case of high power and VF control, which can easily cause motor oscillation. When inverter is in terminal control mode (F00.02=1), this function code is used to select whether JOG command has top priority.

For terminal jog priority (F15.39=1), inverter changes to jog running status after jog terminal is enabled, even if inverter is running; if F15.39=0, inverter can not change to jog running status from running status directly. 220 Function Parameter Description Name of Function Code Unit Default Property Code F15.35 Overmodulation Intensity 1.00 - 1.10 1.05 ● Function Name of Function Code Parameter Description Unit Default Property Code F15.36 PWM Modulation Method Switching Options 0: Disabled (7 preset PWM modulation) 1:

Enabled (5 preset PWM modulation) 0 〇 F15.37 PWM Modulation Method Switching Frequency 0.00 - Maximum Frequency F00.16 Hz 15.00 ● Function Code Name of Function Parameter Description Unit Default Property Code F15.38 Deadband Compensation Mode 0: Disabled 1: Compensation Mode 1 2: Compensation Mode 2 1 〇 Function Parameter Name of Function Code Unit Default Property Code Description F15.39 Terminal Jog Priority 0: Disabled 1: Enabled 0 〇