sinee — 7.17 F16 Group: User Defined Function Parameter

EM600 High-Performance Vector Control Inverter User Manual 2 1 3 4 5 6 7 8 9 10 11 Pulse Input Count Value 2 1 3 4 5 6 7 8 9 9 0 0 Clear Disabled Enabled Length Reach Disabled Enabled Disabled Figure 7-41 Fixed Length Count (Example) Figure 7-41 shows an example, in which F16.01=2 and F16.02=4.0. When length count reaches 8(=2Ч4), “16: Length Reach” is enabled; when “39: Length Clear” is enabled, the count will be cleared and “16: Length Reach” output is disabled. EM600 inverter supports count function (refer to Figure 7-42). Pulse information is inputted via numeric input terminal. When count reaches set value, corresponding signal will be outputted.

User can perform programming with this signal (for example input it via DI/VX to be used as stop command). User can view present count value via F18.33 in real time. F18.33 DI “ Count ” Input (Function of No.34) DO “ Designated Count Value Reach ” Output (Function of No.15) Designated Count Value Reach Signal Pulse Information HDI “ Rapid Count ” Input (Function of No.35) Clear Pulse Count n Cntin Comparer 1 ≥ Designated Count Value Reach Signal Comparer 2 ≥ DO “ Set Count Value Reach ” Output (Function of No.14) Reset DI 揅 ounter Clear? Input ≤ ≤ 0 Designated Count Value n1 (1 - 65535) Set Count Value n2 (1 - 65535) Figure 7-42 Block Diagram of Count Function Principle of work:

When certain information is inputted in the form of pulse. DI terminal collects the information about input pulse number n , and then compare it with the Count Clear Signal (Function of No.36) “Designated Count Value” 1 n . If 1 n n  , it means that “Set Count Value” has not been reached, otherwise it finishes and this result is outputted in the form of terminal DO. Continue count and compare it with “Set Count Value” 2 n . If 2 n n  , it means that “Set Count Value” has not been reached, otherwise it finishes and this result is outputted in the form of terminal DO with count stopping. “36: Counter Clear” is used to clear counter and reset output signal.

If pulse frequency is greater than 250 Hz (=1/(2(default filter times)*2*1ms -1 )), please complete input via X7 and set F02.06 as “35: High-Speed Count Input”. 250 Hz is just a theoretical value. Actual value will apply. To avoid any mistake, please use high speed pulse input terminal. 222 Function Name of Function Code Parameter Description Unit Default Property Code F16.03 Set Count Value F16.04 - 65535 1000 ● F16.04 Designated Count Value 1 - F16.03 1000 ●