sinee — EM730 User Manual

User Manual of EM730/EM730E Series Inverter In the torque mode, the torque is directly set by the digital potentiometer. See F12.43 for the specific value. For diversified torque applications, the EM730/EM730E series inverter supports the multi-segment torque function. Specifically, the input terminal functions “17: multi-segment torque terminal 1” and “18: multi-segment torque terminal 2” need to be set. See the instruction Table 7-21 for details. Table 7-21 Combination of Multi-segment Torque Command and Multi-segment Torque Terminal torque control.

The motor speed can be changed gently by setting the acceleration and deceleration time of F13.06 represents the time for the torque current to rise from 0 to the rated torque current or fall from the rated current to 0. 247 Function code Default Function code name Parameter description Unit Attribute setting F13.03 Multi-segment torque 1 -200.0 - 200.0 % 0.0 ● F13.04 Multi-segment torque 2 -200.0 - 200.0 % 0.0 ● F13.05 Multi-segment torque 3 -200.0 - 200.0 % 0.0 ● 18: multi-segment 17:

multi-segment Number of Segments Torque setting torque terminal 2 torque terminal 1 Invalid Invalid Multi-segment torque 1 Depending on the F13.01 setting Invalid Valid Multi-segment torque 2 F13.03 Valid Invalid Multi-segment torque 3 F13.04 Valid Valid Multi-segment torque 4 F13.05 Function Default Function code name Parameter description Unit Attribute code setting F13.06 Torque control acceleration and deceleration time 0.00 - 120.00 s 0.05 ● Function Default Function code name Parameter description Unit Attribute code setting F13.08 Upper frequency limit options of torque control 0: set by F13.09 1: AI1 2: AI2 3: retention 0 〇