User Manual of EM730/EM730E Series Inverter F13.08=0: depending on F13.09 The upper frequency limit depends on F13.09 during torque control. F13.08=1:AI1 F13.08=2:AI2 The upper frequency limit in torque control is AI (percentage) * F13.09. meaning. 100.00% is the percentage to the set value of F13.09 (upper frequency limit of torque For the details of AI1 and AI2, refer to the F00.04 description. They have the same control). F13.08=5: High-frequency pulse input (X5) The upper frequency limit in torque control is HDI (percentage) * F13.09. meaning.

100.00% is the percentage to the set value of F13.09(upper limit frequency of torque For the details of AI1-AI2 and X5, refer to the F00.04 description. They have the same control). F13.08=6 or 7: communication setting The torque depends on the communication and the like.  If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the upper frequency limit is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient) * F00.18 (upper frequency limit)”, and the 700FH data range is -100.00% to 100.00%, as detailed in Table 12-31. 248 4: retention 5: high frequency pulse input (X5) 6:

communication percentage setting 7: direct communication setting F13.09 Upper frequency limit of torque control 0.50 to maximum frequency F00.16 Hz 50.00 ● F13.10 Upper frequency limit offset 0.00 to maximum frequency F00.16 Hz 0.00 ● F13.18 Reverse speed limit options 0 - 100 % 100 ● F13.19 Speed priority enabling of torque control 0: Disable 1: Enable 1 ●