User Manual of EM730/EM730E Series Inverter In the vector control mode, the dynamic speed response of the inverter is adjusted by changing the speed proportional gain (ASR_P) and speed integral time (ASR_T) of the speed PI regulator. The increase in ASR_P or decrease in ASR_T may accelerate the dynamic response of the speed loop. If ASR_P is too large or ASR_T is too small, however, the system may be over-tuned to cause oscillation. 251 Function Default Function code name Parameter description Unit Attribute code setting F14.52 Stiffness coefficient of speed loop of motor 2 0~20 12 ● In case of any change in F14.52, the default settings of F14.36-F14.39 will change accordingly.
The regulation intensity of the PI regulator for the speed of the motor 2 can be adjusted. Default Function code name Parameter description Unit Attribute There are 21 setting groups of parameters in total. The larger the set value of F14.52, the smaller the integral time is, and the more intense the speed PID regulation is. The smaller the set value