User Manual of EM730/EM730E Series Inverter See F05.00 to F05.06 See F04.19 7.16 Auxiliary Function Parameter Group of F15 Group As shown in Fig. 7-32, when the jog running command (FJOG/RJOG) is valid, the inverter will start running at the set frequency of F15.00; and when the jog running command is invalid, the inverter will be stopped according to the stop mode.

253 mode (Ud = 0, Uq = K * t = F/Fe * 2 * voltage of separation voltage source) F14.81 Multi-point VF frequency F1 of motor 2 0.00 - F14.83 Hz 0.50 ● F14.82 Multi-point VF voltage V1 of motor 2 0.0~100.0 (100.0 = Rated voltage) % 1.0 ● F14.83 Multi-point VF frequency F2 of motor 2 F14.81 - F14.85 Hz 2.00 ● F14.84 Multi-point VF voltage V2 of motor 2 0.0-100.0 % 4.0 ● F14.85 Multi-point VF frequency F3 of motor 2 F14.83 to rated frequency of motor (reference frequency) Hz 5.00 ● F14.86 Multi-point VF voltage V3 of motor 2 0.0-100.0 % 10.0 ● Function Default Function code name Parameter description Unit Attribute code setting F14.87 Stop mode of motor 2 0: Slow down to stop 1:

Free stop 0 〇 Function Function code Default Parameter description Unit Attribute code name setting F15.00 Jog frequency 0.00 to maximum frequency F00.16 Hz 5.00 ● F15.01 Jog acceleration time 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 5.00 ● F15.02 Jog deceleration time 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 5.00 ●