User Manual of EM730/EM730E Series Inverter F15.01 and F15.02 are set as the acceleration and deceleration time during operation. Their values (e.g. 500) depend on the acceleration and deceleration time unit (F15.13), and have different meanings and ranges. For example, F15.13=0 means that the acceleration and deceleration time is 5.00s, and F15.13=1 means that the acceleration and deceleration time is 50.0s. Output frequency Fundamental frequency of acceleration and deceleration time Invalid jog running Jog frequency F15.09 F15.00 0 Actual acceleration time Actual deceleration time Jog acceleration Jog deceleration Time t time F15.01 time F15.02 Fig.
7-32 Schematic Diagram of Jog Running and not shared in normal running, but with the same physical meanings. ★: The separate set frequency and acceleration/deceleration time are applied in jog running, The triggering conditions of the jog running command vary depending on the control mode and valid conditions, as detailed in Table 7-22. Table 7-22 Details of Jog Running Command 254 Vali d jog running Command Source Jog running command Option (F00.02) 1: Terminal control Select the digital input terminal function “4: forward jog (FJOG)” or “5: reverse jog (RJOG)”.
By default, if the function terminal is valid, the jog running command will be valid; and if the function terminal is invalid, the jog running command will be invalid. 2: Communication control If the host writes “0003H: JOG forward” or “0004: JOG reverse” to the register 7000H through the MODBUS protocol, the jog running command will be valid; if it writes “0007H: free stop”, the jog running command will be invalid.