sinee — EM730 User Manual

User Manual of EM730/EM730E Series Inverter the relevant parameters of the connected motor and store them into the internal memory. Fig. 8-18 shows the specific meanings of the parameters of the three-phase asynchronous motor. R1 L1-Lm R2 L2-Lm I1 I2 U1 (1-s)/s*R2 I0 Lm Fig. 8-18 Equivalent Circuit of Three-phase Asynchronous Motor R1, R2, L1, L2, Lm, and I0 in the figure represent: stator resistance, rotor resistance, stator self-inductance, rotor self-inductance, mutual inductance, and no-load excitation current. The leakage inductance is Ls=L-Lm. 8.2 Precautions before Self-identification  Motor parameter self-identification is a process of automatically measuring motor parameters.

The EM730/EM730E series inverter can perform the static and rotary self-identification of motor parameters.  The static self-identification is applicable when the motor load cannot be removed but the motor parameters are available.  The rotary self-identification is suitable when the motor load can be removed. The motor shaft needs to be disconnected from the load before operation. The rotary self-identification must not be performed when the motor is under load.  Prior to self-identification, make sure that the motor is stopped; otherwise, self-identification cannot be performed properly.  Self-identification is valid only in the keyboard control mode (i.e. F00.02=0).

 In order to ensure the normal self-identification of motor parameters, the nameplate parameters (F01.00: motor type; F01.01: rated power of the motor; F01.02: rated voltage of the motor; F01.03: rated current of the motor; F01.04: rated frequency of the motor; F01.05: rated speed of the motor; F01.06: winding connection of the motor; F01.07: rated power factor of the motor) of the controlled motor should be set correctly. When the Y series motor is used based on the specified power of the inverter, its default settings can meet 299