User’s Guide for EM760 series high-performance vector inverter 52 F00.04 Options of main frequency source A 0: digital frequency setting F00.07 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 6: main frequency communication setting (percentage) 7: main frequency communication setting (direct frequency) 0 F00.05 Options of auxiliary frequency source B 0: digital frequency setting F00.07 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 6: auxiliary frequency communication setting (percentage) 7: auxiliary frequency communication setting (direct frequency) 10: process PID 11: simple PLC 0 F00.06 Options of frequency source 0:
main frequency source A 1: auxiliary frequency source B 2: main and auxiliary operation results 3: switching between main frequency source A and auxiliary frequency source B 4: switching between main frequency source A and main and auxiliary operation results 5: switching between auxiliary frequency source B and main and auxiliary operation results 6: Auxiliary frequency source B + feedforward calculation (winding application) 0 〇 F00.07 Digital frequency setting 0.00 to maximum frequency F00.16 Hz 50.00 ● F00.08 Options of main and auxiliary operation 0: main frequency source A + auxiliary frequency source B 1: main frequency source A - auxiliary frequency source B 2:
larger value of main and auxiliary frequency sources 3: smaller value of main and auxiliary frequency sources 4: main frequency source A - auxiliary frequency source B 5: main frequency source A + auxiliary frequency source B 0