sinee — EM760 User Manual

User’s Guide for EM760 series high-performance vector inverter 63 F04 Start/stop control parameter group F04.00 Start-up method 0: direct start 1: start of speed tracking 0  F04.01 Start frequency 0.00~50.00 Hz 0.00  F04.02 Start frequency hold time 0.00-60.00, 0.00 is invalid s 0.00  F04.03 Starting current of DC braking 0.0 to 100.0 (100.0 = rated current of motor) % 50.0  F04.04 Starting time of DC braking 0.00~30.00, 0.00 invalid s 0.00  F04.06 Pre-excitation current 10.0~500.0 (100.0 = no-load current) % 100.0  F04.07 Pre-excitation time 0.00~10.00 s 0.10  F04.08 Speed tracking mode Ones place: Tracking start frequency 0: maximum frequency 1: stop frequency 2:

power frequency Tens place: Selection of search direction 0: search only in command direction 1: Search in the opposite direction if the speed cannot be found in the command direction 01  F04.10 Deceleration time of speed tracking 0.1~20.0 s 2.0  F04.11 Speed tracking current 30.0-150.0 (100.0 = rated current of inverter) % 50.0  F04.12 Speed tracking compensation gain 1.00~10.00 1.00  F04.14 Acceleration and deceleration mode 0: linear acceleration and deceleration 1: acceleration and deceleration of continuous S curve 2:

acceleration and deceleration of intermittent S curve 0  F04.15 Starting time of S curve in acceleration 0.00~325.00 (F15.13=0) 0.0 ~3250.0 (F15.13=1) 0~32500 (F15.13=2) s 1.00 ● F04.16 Ending time of S curve in acceleration s 1.00 ● F04.17 Starting time of S curve in deceleration s 1.00 ● F04.18 Ending time of S curve in deceleration s 1.00 ● F04.19 Stop mode 0: slow down to stop 1: free stop 0  F04.20 Starting frequency of DC braking in stop 0.00 to maximum frequency F00.16 Hz 0.00  F04.21 DC braking current in stop 0.0 to 100.0 (100.0 = rated current of motor) % 50.0  F04.22 DC braking time in stop 0.00~30.00 0.00:

invalid s 0.00  F04.23 Demagnetization time for DC braking in stop 0.00~30.00 s 0.50 