User’s Guide for EM760 series high-performance vector inverter 64 F04.24 Flux braking gain 100-200 (100: no flux braking) 100 F04.26 Start mode after failure/free stop 0: start according to F04.00 setting mode 1: start of speed tracking 0 F04.27 Second confirmation of terminal start command 0: Not required for confirmation 1: to be confirmed 2: Way 2 for no confirmation (no confirmation is made even upon fault resetting) 0 F04.28 Minimum valid output frequency 0.00~50.00 (0.00: function invalid) Hz 0 F04.29 Zero speed check frequency 0.00~5.00 Hz 0.25 ● F04.30 Initial magnetic pole search mode of synchronous motor 0: Invalid 1:
Mode 1 1 ● F05 V/F control parameter group F05.00 V/F curve setting 0: straight line V/F 1: multi-point broken line V/F 2: 1.3-power V/F 3: 1.7-power V/F 4: square V/F 5: VF complete separation mode (Ud = 0, Uq = K * t = voltage of separation voltage source) 6:
VF semi-separation mode (Ud = 0, Uq = K * t = F/Fe * 2 * voltage of separation voltage source) 0 F05.01 Frequency point F1 of multi-point VF 0.00~F05.03 Hz 0.50 ● F05.02 Voltage point V1 of multi-point VF 0.0~100.0 (100.0 = Rated voltage) % 1.0 ● F05.03 Frequency point F2 of multi-point VF F05.01~F05.05 Hz 2.00 ● F05.04 Voltage point V2 of multi-point VF 0.0~100.0 % 4.0 ● F05.05 Frequency point F3 of multi-point VF F05.03 to rated frequency of motor (reference frequency) Hz 5.00 ● F05.06 Voltage point V3 of multi-point VF 0.0~100.0 % 10.0 ● F05.07 Voltage source of VF separation mode 0: digital setting of VF separation voltage 1: AI1 2: AI2 3: AI3 4: high frequency pulse (X7) 5: PID 6:
Communication setting Note: 100% is the rated voltage of the motor. 0 F05.08 Digital setting of VF separation voltage 0.0 to 100.0 (100.0=Rated voltage of motor) % 0.0 ●