User’s Guide for EM760 series high-performance vector inverter 70 gain F07.02 Motor overload pre-alarm coefficient 50~100 % 80 ● F07.03 Motor temperature sensor type 0: No temperature sensor 1: PT100 2: PT1000 3: KTY84-130/150 4: PTC-130/150 0 ● F07.04 Motor overheat protection threshold 0~200 ℃ 110 ● F07.05 Motor overheat pre-alarm threshold 0~200 ℃ 90 ● F07.06 Bus voltage control options Ones place: Instantaneous stop/no-stop function options 0: Invalid 1: deceleration 2: deceleration to stop Tens place: Overvoltage stall function options 0: Invalid 1:
valid 10 F07.07 Voltage of overvoltage stall control 110.0~150.0 (380V, 100.0=537V) % 134.1 F07.08 Instantaneous stop/no-stop operating voltage 60.0 to instantaneous stop/no-stop recovery voltage (100.0 = standard bus voltage) % 76.0 F07.09 Instantaneous stop/no-stop recovery voltage Instantaneous stop/no-stop recovery voltage~100.0 % 86.0 F07.10 Check time for instantaneous stop/no-stop recovery voltage 0.00~100.0 s 0.50 F07.11 Current limit control 0: Invalid 1: limit mode 1 2: limit mode 2 2 F07.12 Current limit level 20.0-180.0 (100.0 = the rated current of inverter) % 150.0 ● F07.13 Quick current limit options 0: Invalid 1:
valid 0 F07.14 Number of retries after failure 0~20, 0: disable retry after failure 0 F07.15 Options of digital output action in retries after failure 0: no action 1: action 0 F07.16 Interval of retries after failure 0.01~30.00 s 0.50 ● F07.17 Restoration time in retries after failure 0.01~30.00 s 10.00 ● F07.18 Options of retries after E08 * E07 * E02 E06 E05 E04 000000