Downloaded from https://www.everyspec.com MIL-HDBK-704-3 TABLE TAC101-I. MIL-STD-704 limits for inrush current, balanced load, power factor, rectification restriction, current distortion, and current spectrum for three phase, 400 Hz utilization equipment. 1/ For utilization equipment being tested to MIL-STD-704 edition B use the unbalanced load limits of MIL-STD-704C. 2/ It is highly recommended that equipment built to MIL-STD-704 editions A, B, C, or D should not use half-wave rectification. 3/ Utilization equipment specification should include requirements that reduce the likelihood of the equipment having an adverse effect on the electrical power characteristics of the aircraft.
Current distortion and current spectrum limits may be imposed to minimize the undesirable effects to the electrical power characteristics. These limits should take into account the utilization equipment power draw, aircraft electrical system capacity and distribution characteristics, trade-offs with weight, volume, cost, and reliability that are specific to each type of equipment and aircraft.
6 Limit 704A 704B 704C 704D 704E 704F Inrush Current N/A N/A N/A N/A N/A 300 Percent for Loads >3 kVA Percent Unbalanced Load Figure 11 MIL- STD- 704A 1/ N/A Figure 1 MIL- STD- 704C Figure 1 MIL- STD- 704D Figure 1 MIL-STD-704E or 3.33% for Loads >30 kVA Figure 1 MIL-STD-704F or 3.33% for Loads >30 kVA Power Factor Figure 12 MIL- STD- 704A N/A N/A N/A N/A 0.85 Lagging to Unity for Loads >500 VA and No Leading Power Factor for > 100VA Rectification Restriction 2/ N/A 2/ N/A 2/ N/A 2/ N/A No Half-Wave Rectification No Half-Wave Rectification Current Distortion See Note 3/ See Note 3/ See Note 3/ See Note 3/ See Note 3/ See Note 3/ Current Spectrum See Note 3/ See Note 3/ See Note 3/ See Note 3/ See Note 3/ See Note 3/