Downloaded from https://www.everyspec.com MIL-HDBK-704-3 time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. 5.1 Compliance test for MIL-STD-704A. For each test condition A through D noted in table TAC105-II, set the amplitude of frequency modulation and rate of change for frequency modulation.

The UUT must remain at the test condition for a length of time that confirms the utilization equipment can continuously operate, and should be at least ten (10) minutes at an average steady state frequency of 400 Hz, at least ten (10) minutes at an average steady state frequency of 384 Hz, and at least ten (10) minutes at an average steady state frequency of 416 Hz. During the test condition, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions.

Record voltage, average frequency, amplitude of frequency modulation, rate of change for frequency modulation, time duration at test condition, and the performance of the UUT for each test condition in the data sheet shown in table TAC105-III. Repeat for each mode of operation of the UUT. 5.2 Compliance test for MIL-STD-704B, C, & D. For each test condition A through E noted in table TAC105-II, set the amplitude of frequency modulation and rate of change for frequency modulation. The UUT must remain at the test condition for a length of time that confirms the utilization equipment can continuously operate.

For test condition A, the UUT must remain at the test condition for a length of time that confirms the utilization equipment can continuously operate, and should be at an average steady state frequency of 400 Hz for at least thirty (30) minutes. For test condition B through E, the UUT must remain at the test condition for a length of time that confirms the utilization equipment can continuously operate and should be at least ten (10) minutes at an average steady state frequency of 400 Hz, at least ten (10) minutes at an average steady state frequency of 395 Hz, and at least ten (10) minutes at an average steady state frequency of 405 Hz.

At each test condition, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record voltages, average frequency, amplitude of frequency modulation, rate of change for frequency modulation, time duration at test condition, and the performance of the UUT for each test condition in the data sheet shown in table TAC105-III. Repeat for each mode of operation of the UUT. 5.3 Compliance test for MIL-STD-704E & F.

For each test condition A through E noted in table TAC105-II, set the amplitude of frequency modulation and rate of change for frequency modulation. The UUT must remain at the test condition for a length of time that confirms the utilization equipment can continuously operate, and should be at least ten (10) minutes at an average steady state frequency of 400 Hz, at least ten (10) minutes at an average steady state frequency of 395 Hz, and at least ten (10) minutes at an average steady state frequency of 405 Hz.

During the test condition, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record voltages, average frequency, amplitude of frequency modulation, rate of change for frequency modulation, time duration at 27