Saving Energy with Frequency Converters 121 Application: Elevator in residential building Load: 1100 kg Operation: 1h per day η gear =90% η Hoist way =80% η Motor =88% (IE2) η AIC =95% η VSD =97% Standby losses: AIC = 40 W, VSD = 40W Result: Table 4.2 Energy consumption for elevator example The values used in the example are very conservative. It may be surprising but one hour operation is very high for an elevator in a typical residential building. Nevertheless the energy balance is negative. This illustrates that applications where potentially AIC can be used require special consideration.

AFE/AIC Standard VSD Losses motor per year 47 kWh 34 kWh Losses standby per year 336 kWh 168 kWh Generated Energy per year 170 kWh – Balance 213 kWh 202 kWh