120 Saving Energy with Frequency Converters 13.16 kW 10.23 kW 11 kW 550 W 451 W 1155 W 770 W Fig. 4.20 System losses during motor operation 7.73 kW 10.23 kW 9.51 kW 476 W 312 W 999 W 716 W Fig. 4.21 System losses at regenerative operation The losses caused by the AFE or AIC itself are much higher than for a standard FC due to the active rectifi er whose losses can be twice as high in operation but also in standby. Depending on the construction, regenerative FC’s without the necessary fi lters create more harmonic currents, which can also lead to higher losses in the grid. Occurrence The more often the motor is operated in regenerative mode the more energy is fed back to the grid.
Therefore situations during a load cycle where energy is generated must be considered. As well as the load cycle itself, the number of load cycles defi nes the resulting amount of energy for a given time. The majority of applications will never justify an investment in AIC which are typically more costly than standard inverters. The example of an elevator illustrates that AIC can also have a negative impact even though elevators are usually seen as the optimal application for AIC.