veda — Facts Manual

119 Saving Energy with Frequency Converters 4. 9 Using Regenerated Power Electric motors can be operated in generative mode when e.g. an asynchronous motor runs faster than its synchronous speed. This can happen when decelerating the motor from one speed to another. In most cases, the user will then channel the generated energy into braking resistors which will convert it into heat. In practice, there are two common technical solutions to feed this energy back into the grid or to supply it to other machines: Intermediate circuit coupling Some FC’s are able to interlink their DC intermediate circuit with the intermediate circuits of other devices.

This enables other devices to be directly supplied with regenerated energy. However, there are some constraints that should be noted. For example, users should always ensure that, if one device short circuits, it will not damage the others. Users must, of course, also take note of what happens if all coupled devices emit regenerated energy at the same time. Power feedback (regenerating) Active Front End or Active Infeed Converters can feed regenerated power back into the grid. If the use of regenerative devices is economic depends on 3 factors: Available energy Most applications generate energy during deceleration processes. This energy decreases continuously during the speed change.

Theoretically, the regenerated energy is equal to 50% of the diff erence between the energy which is in the system when starting and stopping the deceleration, but in reality this fi gure lies somewhere between 10 and 20%. Exceptions to this are seen in lifts, cranes and hoists. Furthermore the nominal motor performance is not equal to the regenerated energy as oversizing of motors is common practice. Only very rarely does the nominal motor power hit exactly the required application power. Losses Motor, cables, gears and even the AIC itself create losses which reduce the energy which can be fed back into the grid.