118 Saving Energy with Frequency Converters LCC = Cic + Cin + Ce + Co + Cm + Cs + Cenv + Cd C ic = initial capital cost (procurement cost) C in = installation and commissioning costs C e = energy cost Cs = downtime and lost production costs C o = operating cost Cenv = environmental cost C m = maintenance cost Cd = decommissioning and disposal costs One of the biggest factors in the life cycle cost formula is the energy cost.
Higher Investments which bring the energy consumption down will, in many applications, have only a minor impact • Fan1 (IE4) • Fan1 (IE2) • Fan1 (IE3) • Fan2 (IE4) Fan1 (IE4 motor) Fan1 (IE2 motor) Fan1 (IE3 motor) Fan2 (IE4 motor) System efficiency [%] Part load ratio Fig. 4.19 Measurement of diff erent ventilator fan systems with 3 kW acc. DIN EN ISO 5801 in same ventilation unit Fan 1 is a direct-driven type and the system effi ciency increases when more effi cient motors (better IE class) are used. Fan 2 is EC fan with a high-effi ciency motor. The lower system effi ciency results from the fan design.
As the motor is placed as hub in the EC fan the air fl ow is disturbed and the system effi ciency decreases. The majority of applications are suitable for speed control but it must be validated case by case. For example, not all compressors are designed for speed control and their minimum and maximum speed limits must be respected and too short or too fast ramp times can be critical.