129 Electromagnetic Compatibility Control cables and serial communication cables should normally be grounded at both ends. Never terminate shield through pigtail. Earth potential between PLC and drive: Disconnect cables and measure voltage with voltmeter to check. Use equalizing cable or make sure units are bolted together. 50/60 Hz ground loop: Use current clamp meter to check. => Ground one end through 100 nF capacitor with short leads. Potential equalizing currents in serial communication cable shield between two drives: => Connect one end of the shield to the special shield connection terminal with RC decoupling. Remember ”correct” pigtail installation! Fig. 5.
9 Grounding of cable shield