130 Electromagnetic Compatibility 5.4 Installations with Frequency Converters It is important to follow good engineering practice when installing frequency converters for ensuring electromagnetic compatibility. When designing an installation, an EMC plan can be made following these steps:

• List components, equipment and areas • Divide into potential noise sources and potentially sensitive equipment • Classify the cables connecting the equipment (potentially noisy or potentially sensitive) • Set requirements and select the equipment • Separate potential noise sources from potentially sensitive equipment • Control interfaces between noise sources and sensitive equipment • Route cables according to the classifi cation Fig. 5.10 Typical measures in practice in a simple frequency converter installation