144 Mains Interference The integer multiples of the fundamental frequency ω1 are called harmonics. The RMS value of a non-sinusoidal waveform (current or voltage) is expressed as: I RMS = h max I 2 h 1 Σ (h) The amount of harmonics in a waveform gives the distortion factor, or total harmonic distortion (THD), represented by the ratio of RMS of the harmonic content to the RMS value of the fundamental quantity, expressed as a percentage of the fundamental: THD = h max I h h 2 I 1 Σ 2 u 100 % Using the THD, the relationship between the RMS current IRMS and the fundamental current I1 can be expressed as: I RMS = I 1 u — 1 + THD 2 The same applies for voltage. The true power factor PF (λ) is:
PF = P In a linear system the true power factor is equal to the displacement power factor: S PF = DPF = cos( M ) In non-linear systems the relationship between true power factor and displacement power factor is: PF = DPF — 1 + THD 2 The power factor is decreased by reactive power and harmonic loads. Low power factor results in a high RMS current that produces higher losses in the supply cables and transformers. In the power quality context, the total demand distortion (TDD) term is often encountered. The TDD does not characterise the load, but it is a system parameter.