145 Mains Interference TDD expresses the current harmonic distortion in percentage of the maximum demand current IL. 2 u 100 % THD = h max I h h 2 I L Σ Another term often encountered in literature is the partial weighted harmonic distortion (PWHD). PWHD represents a weighted harmonic distortion that contains only the harmonics between the 14th and the 40th, as shown in the following defi nition. Σ PWHD = h 40 I h 2 u 100 % h=14 I 1 7.1.3 The Eff ect of Harmonics in a Power Distribution System The picture below shows an example of a small distribution system. A transformer is connected on the primary side to a point of common coupling PCC1, on the medium voltage supply.
The transformer has impedance Z xfr and feeds a number of loads. The point of common coupling where all loads are connected together is PCC2. Each load is connected through cables that have respective impedance Z1, Z2, Z3. Fig. 7.4 Example of Distribution System