146 Mains Interference Harmonic currents drawn by non-linear loads cause distortion of the voltage, due to the voltage drop on the impedances of the distribution system. Higher impedances result in higher levels of voltage distortion. Current distortion relates to apparatus performance and it relates to the individual load. Voltage distortion relates to system performance. It is not possible to determine the voltage distortion in the PCC knowing only the harmonic performance of the load. In order to predict the distortion in the PCC the confi guration of the distribution system and relevant impedances must be known.
A commonly used term for describing the impedance of a grid is the short circuit ratio Rsce, defi ned as the ratio between the short circuit apparent power of the supply at the PCC (S sc ) and the rated apparent power of the load (S equ ). R sce = S ce S equ where S sc = U 2 Z supply and S equ = U Ч I equ The negative eff ect of harmonics is twofold • Harmonic currents contribute to system losses (in cabling, transformer) • Harmonic voltage distortion causes disturbance to other loads and increase losses in other loads Non-linear System Impedance Current Voltage Contribution to system losses Disturbance to other users Fig. 7.5 Negative Eff ects of Harmonics: System Losses and Disturbance