149 Mains Interference 7.3.1 Passive Harmonic Mitigation DC inductors DC inductors are placed in the DC link between the rectifi er and the bulk DC capacitor. It is possible to use a single inductor in either the + or the – side or use two inductors. This solution reduces THDi to values between 35 and 45%. AC inductors AC inductors are placed on the line side of the rectifi er. Their harmonic performance is similar to DC inductors and reduce THDi to typical values of between 35 and 45%, depending on the size of the inductor. DC vs. AC inductors Since DC and AC inductors have similar harmonic performance levels the question about the diff erences between the two solutions often arises.
First of all, even if the THD value is similar, the eff ect of the two solutions on the components of the harmonic spectrum is diff erent. DC inductors attenuate more the low frequency components (5th, 7th, 11th harmonic) while the AC inductors have a better performance for higher harmonic orders. Across inductors an AC voltage drop occurs. In the case of AC inductors, a voltage drop will occur, typically around 4%. In the case of DC inductors, the DC current does not cause a voltage drop. The only voltage drop across DC inductors results from the current ripple of the rectifi er.
Consequently, using DC inductors will result in a higher DC link voltage, thus the ability to provide more torque at the motor shaft. This is the major advantage of DC inductors. The main advantage of AC inductors is that they protect the rectifi er against transients from the mains. Passive harmonic fi lters Passive harmonic fi lters are connected in series with the mains supply. They can be realised with various circuit topologies that typically consist of combinations of inductors (L) and capacitors (C), sometimes also damping resistors R. The fi lter circuit can be a low-pass circuit, tuned to specifi c harmonics (5th, 7th, etc.) or slightly de- tuned, to avoid the risk of resonances.
The performance of passive fi lters depends on the specifi c frequency converter’s DC link confi guration (with/without DC chokes, value of capacitance) and a performance level can be assured for a specifi c confi guration. Danfoss Advanced Harmonic Filters (AHF) are designed specifi cally for Danfoss VLT® frequency converters and can reduce THD to 10 % (AHF10 series) or even 5% (AHF 5 series). These fi lters use a proprietary topology with a two-stage de-tuned LC harmonic- absorbing circuit.