veda — Facts Manual

150 Mains Interference Passive fi lters have the disadvantage of being quite bulky (comparable in size with the FC). They have a capacitive power factor that needs to be considered during system level design for avoiding resonances. Multi-pulse rectifi ers Multi-pulse rectifi ers are fed from phase- shift transformers. The most common solutions are with 12 pulses (2 x 3 phases) or 18 pulses (3 x 3 phases). Through phase- shifting, low order harmonics are in 180° opposition, cancelling each other. For example, in the case of 12 pulse rectifi cation the phases of the secondary have a 30° phase off set (the off set between the D and Y windings).

In this confi guration the 5th and 7th harmonics are cancelled and the largest harmonics will be the 11th and 13th. Multi-pulse harmonic mitigation requires large transformers – larger than the FC. Another disadvantage is that the performance is reduced in non-ideal conditions such as voltage imbalance. 7.3.2 Active Harmonic Mitigation Active Front End (AFE) The diode rectifi er can be replaced with an inverter with active switches (usually IGBT transistors), similar to the inverter at the motor side. The grid-side inverter is pulse-width modulated and the input current is nearly sinusoidal. The harmonics of the mains frequency are not present.

On the other hand the switching frequency components are injected to the mains grid. In order to reduce the switching noise a passive fi lter is used, usually in a low-pass L-C-L topology (two inductors and capacitors between the inductors). The main advantage of the AFE is that it allows four-quadrant operation: that means that the energy fl ow is bi-directional and in the case of regenerative braking the energy can be injected back to the grid. This is advantageous in applications with frequent braking or long-time braking such as cranes or centrifuges. The disadvantage of the AFE solution is a relatively low effi ciency and a high complexity.

When the application does not require bi-directional energy fl ow the energy effi ciency of the AFE is inferior to an active fi lter solution. Active fi lters Active fi lters (AF) consist of an inverter that generates harmonic currents in anti-phase with the harmonic distortions on the grid thus achieving a 180° cancellation eff ect. The operation principle is illustrated in the illustration below, where the AF cancels the harmonic currents from a diode rectifi er.