151 Mains Interference ~~ ~ Load Control Fig. 7.6 Operation Principle of an Active Filter As in the case of AFE, an LCL fi lter is needed to eliminate the noise at the switching frequency. Active fi lters are connected in parallel with the non-linear (harmonic generating) load. This allows for several harmonic mitigation possibilities: • Individual compensation of non-linear loads: an active fi lter compensates harmonics from a single load. Danfoss off ers an optimised fi lter + FC package called “Low Harmonic Drive (LHD)” • Group compensation: harmonics from a group of several loads (for example FC’s) are compensated by a single fi lter • Central compensation:
harmonics are compensated directly at the point of common- coupling of the main transformer Supply Central compensation M 3- M 3- M 3- Group compensation M 3- Individual compensation Fig. 7.7 Harmonic compensation can take place in diff erent areas of the network M 3-