171 Sizing ad Selection of Frequency Converters In the diagram 9.5 Power reduction diagram for switching frequency and temperature, the switching frequency of the inverter is plotted on the X axis. The output current (in %) of the unit is plotted on the Y axis. Higher switching frequencies result in less irritating motor noise levels. However, the power dissipation in the inverter increases with the switching frequency, leading to additional heating of the unit. Reducing the switching frequency allows the switching losses to be reduced. If the switching frequency is too low, the motor tends to run less smoothly.
The switching frequency is thus always a compromise between noise generation, smooth running, and losses. If, for example a unit is operated at an ambient temperature of 45°C, it can continuously deliver 100% of its rated output current at a switching frequency of 4 kHz. If the ambient temperature increases to 55°C, a current of only around 75% is possible in continuous operation without a reduction of life-time. If the reduction of life-time is not acceptable, a larger FC with suffi cient power reserve must be used. Power derating curves must be observed not only at elevated temperatures, but also at reduced air pressures, such as when FC’s are used at elevations above 1000 metres.
9.6 Regenerative Energy If a motor is driven by an FC that during deceleration the rotor will run faster than the rotating magnetic fi eld causing the motor to act as a generator. Depending on how much energy is fed back from the motor and how often, various measures must be taken. If the power exceeds the total power losses of the motor and the FC, the intermediate circuit voltage will increase until, at a defi ned voltage, the FC disables its output and consequently loses the control of the motor. Speed Motor shaft frequency FC output frequency Load torque Start Stop Fig. 9.6 Start/Stop illustrations for regenerative principle